BIOS and System Programming
64 VIPA GmbH CP486 00/14
4.3 System Register
4.3.1 CP-Status Register (I/O-Address 280 hex - read only)
status
Bit 0 /PLC bank interrupt 0 INT 12 was triggered via PLC-access to
element 1023 in the current bank
1 no access to bank element 1023 via PLC
Bit 1 /WD reset 0 error: watchdog has announced
1 no error
Bit 2 /PFO (accu supervision) 0 CP accu voltage under 2.5V (accu empty
or defective)
1 CP accu voltage over 2.5V (accu ok)
Bit 3 reserved reserved
Bits 4 - 7 indicate settings of DIP switch S2 (boot defaults at accu failure) :
Bit 4 DIP switch S2 position 1 0 no boot from floppy disk drive
1 boot from floppy disk drive A
Bit 5 DIP switch S2 position 2 0 boot from silicon disk as disk drive A
1 boot from memory card as disk drive A
Bit 6 DIP switch S2 position 3 0 bank on PLC side not visible
1 8 banks on PLC side (32-39) visible
Bit 7 DIP switch S2 position 4 reserved
4.3.2 PLC-Status Register (I/O-Address 281 hex - read only)
Bit 0 CPKL 0 PLC has started
1 PLC in RESET mode (approx. 1.6sec)
Bit 1 BASP 0 outputs are conducted
1 outputs are deactivated
Bit 2 BAU 0 PLC battery is ok
1 PLC battery has failed
Bit 3 NAU 0 power supply connected to PLC
1 power supply for PLC is off
Bit 4 PC type (of DIP-SW) 0 PLC-135/PLC-155 set up
1 PLC-115 set up
Bit 5 reserved
Bit 6 reserved
Bit 7 reserved